903.2 Where required.
Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.13.
Exceptions:
1. Sprinklers shall not be required in electrical equipment rooms where all of the following conditions are met:
1.1. The room is dedicated to electrical equipment only.
1.2 Only dry-type electrical equipment is used.
1.3 Equipment is installed in a 2-hour fire-rated enclosure including protection for penetrations.
1.4 No combustible storage is permitted to be stored in the room.
2. Sprinklers shall not be permitted in elevator machine rooms and elevator machinery spaces.
3. Sprinklers shall not be required in rooms and spaces protected by an alternative fire suppression system in accordance with the New York City Fire Code and Section 904 of this code.