Limited Sprinkler & Standpipe Alterations Limited Alteration Application - NYC - New York City

Writer: Built EngineersBuilt Engineers




An alteration to a sprinkler system that is limited in scope that a licensed Fire Suppression Piping Contractor can do, falling into one of the following categories:

Category – 1

There is a $35,000 cost limitation in any 12 month period and only the following work can be done:

Category – 1 $35,000 cost limitation per building including appliance and labor in any 12 month period

  1. Changes that do not alter the type of sprinkler system

  2. New Sprinkler Heads: Install up to five new sprinkler heads off of an existing sprinkler system

  3. Rearrange Sprinkler Heads: Rearrange not more than 20 sprinkler heads in areas classified in light hazard occupancy, in restaurant service areas classified in Group 1 ordinary hazard occupancy, or in mercantile areas classified in Group 2 ordinary hazard occupancy

  4. Relocation of piping that does not affect the operation of the sprinkler system

  5. Replacement of parts required for the operation of a sprinkler system

Category – 2

No cost and time period limitation, but only the following work can be done:

Category – 2 Estimated cost of unlimited work, must include all appliance and labor costs

  1. Sprinkler Heads for Existing Sprinkler System: Replacement of sprinkler heads, provided that orifice sizes, type and deflector positions remain the same

Limited Standpipe Alterations

An alteration to an existing combined standpipe system that a licensed Fire Suppression Piping Contractor can do:

Category – 1 There is a $35,000 cost limitation in any 12 month period and only the following work can be done:

Category – 1

$35,000 cost limitation per building including appliance and labor in any 12 month period;

  1. Relocate Hose Source and Cabinets: Relocation of standpipe auxiliary hose sources and cabinets within 10 ft. of original location provided existing covered area is not affected Relocation must comply with the NYC Code requirements for a new installation

  2. Replace Parts: Replacement of parts required for operation of a combined standpipe system


Category – 2 No cost and time period limitation, but only the following work can be done:

Category – 2

Estimated cost of unlimited work, must include all appliance and labor costs

N/A


For use only with LAA Applications submitted on or after December 31, 2014.

  • Category 1 LAA Fee Chart for One- and Two Family Homes

  • Category 2 LAA Fee Chart for 1, 2, 3 Family Fees

Only one category and one work type can be filed per limited alteration application.


 
 
 

Comments


Get A Proposal

GET A PROPOSAL

Upload Project Documents
Upload supported file (Max 15MB)
Upload Images
Upload supported file (Max 15MB)

For any inquiries, questions, or recommendations, please call 646.481.1861 or send us an email and we'll get the ball rolling from there.

To apply for a job with BUILT Engineers, please send a cover letter together with your resume.

BUILT Engineers

447 Broadway, 2nd Floor #A200

New York, NY 10013

 

info@builtengineers.com

646.481.1861

© 2021 by BUILT ENGINEERS

Talk to a Licensed Professional Engineer today: 646.481.1861

  • LinkedIn
  • Instagram
bottom of page